1: Product features and usage:
this product is suitable for the AC rated voltage 450 / 750V and below electrical instruments and automatic control system transmission line, with oil resistance, waterproof, wear resistance, acid and alkali resistance and a variety of corrosive gases, aging resistance, non-combustion and other excellent performance, suitable for metallurgy, electric power, petrochemical and other industries.
2: Product implementation standards
Q/HHTZH004.1
Flame retardant and fire resistance characteristic test follows the GB12666-90 standard
Three: Characteristics
1. AC rated voltage: U0 / U 450 / 750KV
2. Operating temperature: the insulation of polyperfluoroethylene propylene (F46) shall not exceed 200℃
Soluble polytetrafluoroethylene (PFA) insulation shall not exceed 260℃
3. Ambient temperature: PVC sheath: fixed laying-40℃, non-fixed laying-15℃
Fluorinated plastic and silicone rubber sheath: fixed laying-60℃, non-fixed laying-20℃
4. The cable installation and laying temperature shall not be less than 0℃ (fluorine plastic, silicone rubber and nitrile sheath cable shall not be less than-25℃).
5. Allowable bending radius of the cable: the unarmored cable is 6 times of the outer diameter of the cable
Copper strip shielding or steel strip armored cable is 12 times the outer diameter of the cable
Fluorinated plastic insulated and sheathed cables are 8 times the outer diameter of the cable